{"schemaVersion":1,"url":"https://cve.openhack.com/cve/CVE-2024-5659","id":"CVE-2024-5659","title":"Rockwell Automation Multicast Request Causes major nonrecoverable fault on Select Controllers","description":"Rockwell Automation was made aware of a vulnerability that causes all affected controllers on the same network to result in a major nonrecoverable fault(MNRF/Assert). This vulnerability could be exploited by sending abnormal packets to the mDNS port. If exploited, the availability of the device would be compromised.","descriptionLong":"Rockwell Automation was made aware of a vulnerability that causes all affected controllers on the same network to result in a major nonrecoverable fault(MNRF/Assert). This vulnerability could be exploited by sending abnormal packets to the mDNS port. If exploited, the availability of the device would be compromised.","published":"2024-06-14T16:42:20.699Z","updated":"2026-06-17T08:16:22.800Z","reserved":"2024-06-05T16:47:18.275Z","status":"Analyzed","rejected":false,"assigner":"Rockwell","metric":{"version":"4.0","score":8.3,"vector":"CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:H","rating":"high","source":"Rockwell"},"metrics":[{"version":"4.0","score":8.3,"vector":"CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:H","rating":"high","source":"Rockwell"},{"version":"4.0","score":8.3,"vector":"CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:H/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X","rating":"high","source":"rockwellautomation.com"},{"version":"3.1","score":6.5,"vector":"CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H","rating":"medium","source":"NVD"}],"rating":"high","products":["Rockwell Automation ControlLogix® 5580","Rockwell Automation GuardLogix 5580","Rockwell Automation 1756-EN4","Rockwell Automation CompactLogix 5380","Rockwell Automation Compact GuardLogix 5380","Rockwell Automation CompactLogix 5480"],"affectedProducts":[{"vendor":"Rockwell Automation","product":"ControlLogix® 5580","defaultStatus":"unaffected","versions":[{"status":"affected","version":"34.011"}],"platforms":[]},{"vendor":"Rockwell Automation","product":"GuardLogix 5580","defaultStatus":"unaffected","versions":[{"status":"affected","version":"34.011"}],"platforms":[]},{"vendor":"Rockwell Automation","product":"1756-EN4","defaultStatus":"unaffected","versions":[{"status":"affected","version":"4.001"}],"platforms":[]},{"vendor":"Rockwell Automation","product":"CompactLogix 5380","defaultStatus":"unaffected","versions":[{"status":"affected","version":"34.011"}],"platforms":[]},{"vendor":"Rockwell Automation","product":"Compact GuardLogix 5380","defaultStatus":"unaffected","versions":[{"status":"affected","version":"34.011"}],"platforms":[]},{"vendor":"Rockwell Automation","product":"CompactLogix 5480","defaultStatus":"unaffected","versions":[{"status":"affected","version":"34.011"}],"platforms":[]}],"packages":[],"cwes":["CWE-670"],"aliases":[],"references":[{"url":"https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1673.html","tags":["x_transferred","Vendor Advisory"]}],"patchReferenced":false,"fixAvailable":false,"exploitReferenced":false,"kev":false,"kevAdded":null,"kevDue":null,"kevEntry":null,"ssvc":{"exploitation":"none","automatable":"yes","technicalImpact":"partial"},"epss":0.00311,"epssPercentile":0.2451,"sources":[{"name":"CVE List","url":"https://www.cve.org/CVERecord?id=CVE-2024-5659","ok":true},{"name":"NVD","url":"https://nvd.nist.gov/vuln/detail/CVE-2024-5659","ok":true,"note":"Analyzed"},{"name":"OSV","url":"https://osv.dev/vulnerability/CVE-2024-5659","ok":false,"note":"no open-source package data"},{"name":"CISA KEV","url":"https://www.cisa.gov/known-exploited-vulnerabilities-catalog","ok":true,"note":"not listed"},{"name":"EPSS","url":"https://api.first.org/data/v1/epss?cve=CVE-2024-5659","ok":true,"note":"scored 2026-11-19"}],"aiTitle":false,"tech":[],"critical":[],"attention":null}