External Control of Critical State Data (CWE-642) in the Controller 6000 and Controller 7000 diagnostic web interface allows an authenticated user to modify device I/O connections leading to unexpected behavior that in some circumstances could compromise site physical security controls. Gallagher recommend the diagnostic web page is not enabled (default is off) unless advised by Gallagher Technical support. This interface is intended only for diagnostic purposes.
9.10 prior to vCR9.10.240520a (distributed in 9.10.1268(MR1)), 9.00 prior to vCR9.00.240521a (distributed in 9.00.1990(MR3)), 8.90 prior to vCR8.90.240520a (distributed in 8.90.1947 (MR4)), 8.80 prior to vCR8.80.240520a (distributed in 8.80.1726 (MR5)), 8.70 prior to vCR8.70.240520a (distributed in 8.70.2824 (MR7)), all versions of 8.60 and prior.
Summary
AIThe diagnostic web interface on affected Gallagher Controller 6000 and Controller 7000 devices lets an authenticated user modify device I/O connections. If the interface is enabled, this can cause unexpected behavior and, in some circumstances, compromise site physical security controls.
Who should check
Operators of Gallagher Controller 6000 or 7000 running 9.10, 9.00, 8.90, 8.80, or 8.70 before the respective fixed versions, or any version of 8.60 or earlier, should check their devices.
What to do
- 1Update to vCR9.10.240520a (in 9.10.1268 MR1), vCR9.00.240521a (in 9.00.1990 MR3), vCR8.90.240520a (in 8.90.1947 MR4), vCR8.80.240520a (in 8.80.1726 MR5), or vCR8.70.240520a (in 8.70.2824 MR7), as applicable.
- 2Keep the diagnostic web page disabled unless Gallagher Technical Support advises enabling it.
- 3Consult Gallagher’s advisory if running 8.60 or earlier; no fixed version for those releases is listed in the provided information.