KNX devices that use KNX Connection Authorization and support Option 1 are, depending on the implementation, vulnerab…
KNX Association KNX Protocol Connection Authorization Option 1
Actively exploited in the wild
Added to CISA's Known Exploited Vulnerabilities catalog on Jul 15, 2026. US federal agencies must patch by Jul 29, 2026.
Affected versions
| Product | Affected | Fixed in |
|---|---|---|
| KNX Association KNX Protocol Connection Authorization Option 1 |
| No fix yet |
Original description
KNX devices that use KNX Connection Authorization and support Option 1 are, depending on the implementation, vulnerable to being locked and users being unable to reset them to gain access to the device. The BCU key feature on the devices can be used to create a password for the device, but this password can often not be reset without entering the current password. If the device is configured to interface with a network, an attacker with access to that network could interface with the KNX installation, purge all devices without additional security options enabled, and set a BCU key, locking the device. Even if a device is not connected to a network, an attacker with physical access to the device could also exploit this vulnerability in the same way.
From the CVE record · icscert