{"schemaVersion":1,"url":"https://cve.openhack.com/cve/CVE-2022-4608","id":"CVE-2022-4608","title":"HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product: unexpected restart due to a s…","description":"A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow.","descriptionLong":"A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow.","published":"2023-07-26T05:26:42.720Z","updated":"2026-11-10T12:10:00.177Z","reserved":"2022-12-19T09:46:30.033Z","status":"Modified","rejected":false,"assigner":"Hitachi Energy","metric":{"version":"3.1","score":7.5,"vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H","rating":"high","source":"Hitachi Energy"},"metrics":[{"version":"3.1","score":7.5,"vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H","rating":"high","source":"Hitachi Energy"},{"version":"3.1","score":7.5,"vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H","rating":"high","source":"hitachienergy.com"},{"version":"3.1","score":7.5,"vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H","rating":"high","source":"NVD"}],"rating":"high","products":["Hitachi Energy RTU500 series"],"affectedProducts":[{"vendor":"Hitachi Energy","product":"RTU500 series","defaultStatus":"unaffected","versions":[{"status":"affected","version":"RTU500 series CMU Firmware version 13.3.1"},{"status":"affected","version":"RTU500 series CMU Firmware version 13.3.2"},{"status":"unaffected","version":"RTU500 series CMU Firmware version 13.3.3"},{"status":"unaffected","version":"RTU500 series CMU Firmware version 13.4.1"}],"platforms":[]}],"packages":[],"cwes":["CWE-787"],"aliases":[],"references":[{"url":"https://publisher.hitachienergy.com/preview?DocumentID=8DBD000121&LanguageCode=en&DocumentPartId=&Action=Launch","tags":["vendor-advisory"]},{"url":"https://search.abb.com/library/Download.aspx?DocumentID=8DBD000121&LanguageCode=en&DocumentPartId=&Action=Launch","tags":["x_transferred"]}],"patchReferenced":false,"fixAvailable":false,"exploitReferenced":false,"kev":false,"kevAdded":null,"kevDue":null,"kevEntry":null,"ssvc":{"exploitation":"none","automatable":"yes","technicalImpact":"partial"},"epss":0.00712,"epssPercentile":0.54321,"sources":[{"name":"CVE List","url":"https://www.cve.org/CVERecord?id=CVE-2022-4608","ok":true},{"name":"NVD","url":"https://nvd.nist.gov/vuln/detail/CVE-2022-4608","ok":true,"note":"Modified"},{"name":"OSV","url":"https://osv.dev/vulnerability/CVE-2022-4608","ok":false,"note":"no open-source package data"},{"name":"CISA KEV","url":"https://www.cisa.gov/known-exploited-vulnerabilities-catalog","ok":true,"note":"not listed"},{"name":"EPSS","url":"https://api.first.org/data/v1/epss?cve=CVE-2022-4608","ok":true,"note":"scored 2026-11-18"}],"aiTitle":false,"tech":[],"critical":[],"attention":null}