HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product: unexpected restart due to a s…
Hitachi Energy RTU500 series
Affected versions
| Product | Affected | Fixed in |
|---|---|---|
| Hitachi Energy RTU500 series |
|
|
Original description
A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow.