A cleartext transmission of sensitive information vulnerability exists in Schneider Electric's 66074 MGE Network Mana…
Schneider Electric SE 66074 MGE Network Management Card Transverse installed in MGE UPS and MGE STS
Affected versions
| Product | Affected | Fixed in |
|---|---|---|
| Schneider Electric SE 66074 MGE Network Management Card Transverse installed in MGE UPS and MGE STS |
| No fix yet |
Original description
A cleartext transmission of sensitive information vulnerability exists in Schneider Electric's 66074 MGE Network Management Card Transverse installed in MGE UPS and MGE STS. he integrated web server (Port 80/443/TCP) of the affected devices could allow remote attackers to discover an administrative account. If default on device, it is not using a SSL in settings and if multiple request of the page "Access Control" (IP-address device/ups/pas_cont.htm) account data will be sent in cleartext