Siemens ETA4 firmware (all versions prior to Revision 08) of the SM-2558 extension module for: SICAM AK, SICAM TM 170…
Siemens SICAM RTU Devices before 08
Affected versions
| Product | Affected | Fixed in |
|---|---|---|
| Siemens SICAM RTU Devices before 08 |
| No fix yet |
Original description
An issue was discovered in Siemens ETA4 firmware (all versions prior to Revision 08) of the SM-2558 extension module for: SICAM AK, SICAM TM 1703, SICAM BC 1703, and SICAM AK 3. Specially crafted packets sent to Port 2404/TCP could cause the affected device to go into defect mode. A cold start might be required to recover the system, a Denial-of-Service Vulnerability.
From the CVE record · icscert